Product Details:
Brand | Novus |
Voltage | 0 to 50 mVdc. Impedance > 1 M Omega |
Response Time | <500 ms |
Output Type | 4-20 mA current or 20-4 mA, two-wire type; linear in respect to the measured temperature |
Isolation | 1000 Vac for 1 minute between input and output |
ABS enclosure | 44 mm diameter and 24 mm maximum height |
Communication cable | mini-B USB cable, 5 pins |
Total Accuracy | maximum error of 0.3 % of maximum range for thermocouples; 0.2 % of maximum range for Pt100 and vol |
Output Resolution | 0.004 mA (12 bits) |
Power | 12 to 35 Vdc, voltage over the transmitter |
Maximum Load in series | RL= (Vdc - 12) / 0.02 Omega where Vdc is the power voltage |
Input Sensor | configurable |
Relative Humidity | 0 to 90 % RH |
Operating Temperature | -20 to 75 DegreeC |
Eletromagnetic Compatibility | EN 50081-2, EN 50082-2 |